2 TECHS ACTIVE
πΈ
Scanned 4 mins agoSCANNED UNIT NAMEPLATEActive Verification
Actual raw camera capture from Shane's phone vs. decoded equipment specs.
RAW CAMERA CAPTURE
Verified Unit Assignment
RTU-1 (Main Sales Floor)
Manufacturer
CARRIER COMMERCIAL
Size5 TONS
RefrigerantR-410A
Model48TCED06A2A5A0A0
Serial2423U90184
LIVE WORK PROGRESS PHOTOS
Chronological photo log from ShaneTAP TO PAN & ZOOM
1:35 PM(Miniso #US29 - Chino Hills)
Monday, Sep 7th, 2026 β’ 1:35 PM
TAP TO PAN & ZOOM
1:18 PM(Miniso #US29 - Chino Hills)
Monday, Sep 7th, 2026 β’ 1:18 PM
π’ MINISO #US29 β PREVIOUS SERVICE HISTORY
Instant visual history: check what previous technicians diagnosed and repaired before advising the current tech.
Wednesday, Aug 12th, 2026β’ Serviced by TonyRTU-1
Scheduled MaintenanceβReplaced 2-pole 30A contactor. Pitted points causing intermittent voltage drop to compressor.β
Before Repair
Aug 12: Burnt contactor points
Installed OEM
Aug 12: New OEM contactor installed
Thursday, Jun 4th, 2026β’ Serviced by ShaneRTU-1
Emergency CallβCondenser fan motor seized. Replaced 1/2 HP motor and 10MFD capacitor. Cooling verified.β
Before Repair
Jun 4: Seized fan motor wiring
Installed OEM
Jun 4: New motor amp check 2.4A
Current Active Location
Miniso #US29
Miniso #US29, Chino Hills, CA
Total Equipment on Roof: 4 Packaged RTUsπΊοΈ Open Map
π Site Access & Roof Key Note:Key box code 4491. Access ladder located behind trash enclosure.
β‘ 2-SECOND HEALTH CHECK
LIVE BLE TELEMETRYLOW SIDE (SUCTION)VAPOR
118.4 psi
Suction Temp:53.4Β°F
HIGH SIDE (LIQUID)HEAD
338.2 psi
Liquid Temp:95.8Β°F
RETURN AIR TEMPINLET
74.5 Β°F
Return Duct ProbeACTIVE
SUPPLY AIR TEMPSUPPLY
55.3 Β°F
Discharge PlenumACTIVE
Delta-T Coil Drop19.2Β°F
π’COOLING NORMAL(Target 18Β°-22Β°F)
Superheat (SH)12.8Β°F
Subcooling (SC)9.8Β°F
π’REFRIGERANT CHARGE OK
Direct Field Comms with Shane